CHUANWEI FIRECHUANWEI FIREFire protection equipment manufacturer Request a quote

Dry-Pipe Sprinkler System Equipment

Dry Pipe Alarm Valve

A differential-type water control valve for dry-pipe sprinkler systems in unheated or freezing environments. The downstream piping is kept charged with air or nitrogen instead of water; when a sprinkler opens and the system air pressure drops, the valve opens and floods the piping with water.

DN100–DN2004–8 inFlanged1.6 MPa / 16 barAir / Water Differential

Flange drilling, system air-supply pressure and trim arrangement are confirmed against the approved drawing, sample or order schedule before production.

Technical overview

Confirmed construction and operating data

Critical product data is presented in HTML for clear international sourcing. The valve is type-tested to a national standard; no foreign approval is claimed on this page.

Series specifications

Product type
Differential Dry Pipe Alarm Valve
Available sizes
DN100 / 4 in to DN200 / 8 in
Connection options
Flanged
Maximum working pressure
1.6 MPa / 16 bar / approx. 232 psi
Air-to-water differential ratio
approx. 5.5:1 to 7.25:1 (measured)
Reset prevention
Latching mechanism fitted
Alarm device inlet pressure
≥ 0.05 MPa (measured 0.08–0.09 MPa)
Valve body
Ductile iron QT450-10 / ASTM A536 65-45-12
Coating
Internal and external epoxy coating (red)
Weight
Available on request
Type-test standard
GB 5135.4 (national dry-pipe-valve standard); no foreign approval implied
Packaging
Wooden case

Complete supply scope

Alarm trim supplied with the main valve

The standard complete assembly includes the items below. Customer-specified accessory makes or trim arrangements can be reviewed before quotation.

01Dry pipe alarm valve
02Accelerator
03Air pressure gauge
04Water pressure gauge
05Water motor alarm
06Pressure switch
07Exhaust / air vent valve
08Fill / drip valve
09Test valve
10Trim piping & fittings

Available models

Configurations for quotation

International size and connection are the primary selection fields. ZSFC codes are retained only as factory references. Reference height may vary with the approved trim arrangement.

International configurationNominal sizeMaximum pressureReference heightFactory reference
Flanged Dry Pipe Alarm ValveDN100 / 4 in1.6 MPa375 mmZSFC100
Flanged Dry Pipe Alarm ValveDN150 / 6 in1.6 MPa455 mmZSFC150
Flanged Dry Pipe Alarm ValveDN200 / 8 in1.6 MPa610 mmZSFC200

For quotation, specify DN size, flange drilling requirement, system air-supply pressure, trim and accessory requirements, quantity and destination country.

OEM / ODM capability

Configured to the approved drawing or sample

Manufacturing and assembly options are confirmed against the buyer's technical schedule. Connection-standard names describe available machining patterns and do not imply third-party product approval.

Flange machiningGB, ANSI, DIN or BS dimensional patterns, subject to the approved drawing and pressure requirement.
Trim configurationCustomer-specified accessories, accelerator option and agreed component configuration.
Brand presentationCustom nameplate, logo and epoxy coating color.
Drawing or sample productionValve connection and trim details reviewed before manufacturing.
Export packingWooden-case packing prepared according to the order.

Send your dry pipe valve schedule

Include size, air-supply pressure, trim configuration, quantity and destination country.